Product Features :
• Input frequencies to 500 kHz (with line driver input).
• 32-bit counting range.
• 2 or 4 axes operation available.
• 5, 12, 24 V line driver inputs available. (5 and 12 V line driver input is only available for 1 axis with the CS1W-CT021 and 2 axes with the CS1W-CT041).
• Supports simple, ring, and linear counting modes.
• Supports offset phase input, up and down pulse input, and pulse + direction input.
• Supports 4 external control outputs and a total of 16 functions can be set including open gate, close gate, preset, reset, capture, stop/capture/reset combinations, and reset enable.
• One Module supports 4 external outputs and 28 internal outputs with counter value zone comparisons, target comparisons, delays, holds, programmable outputs, and hysteresis settings.
• Pulse rate measurement function and data logging.
• Counter outputs and external control inputs can be used to trigger interrupt tasks in the CPU.
• Settings can be changed during Module operation.